How is OTR parameter (motor torque) expressed as a value via serial communication on the ATV32 drive?
Issue:
Express OTR parameter (motor torque) as a value via serial communication on the ATV32 drive.

Product Line:
ATV32 series drives.

Environment:
All models, All serial numbers.

Cause:
OTR in the drive is displayed as 0 to 300% but 0-300 is not read from the communication registers, the number is different.  How do these correlate?

Resolution:
Motor torque, OTR, is displayed by the drive as percentage of nominal motor torque as a value between 0% and 300%.
When reading motor torque over the network from register 3205, it will be displayed as a value between 0 and 8192.  0 = 0% torque, 8192 = 300% torque.   When the motor is running at nominal torque, reading parameter 3205 will return the number 2731.

Schneider Electric USA

How is OTR parameter (motor torque) expressed as a value via serial communication on the ATV32 drive?
Issue:
Express OTR parameter (motor torque) as a value via serial communication on the ATV32 drive.

Product Line:
ATV32 series drives.

Environment:
All models, All serial numbers.

Cause:
OTR in the drive is displayed as 0 to 300% but 0-300 is not read from the communication registers, the number is different.  How do these correlate?

Resolution:
Motor torque, OTR, is displayed by the drive as percentage of nominal motor torque as a value between 0% and 300%.
When reading motor torque over the network from register 3205, it will be displayed as a value between 0 and 8192.  0 = 0% torque, 8192 = 300% torque.   When the motor is running at nominal torque, reading parameter 3205 will return the number 2731.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.