{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Are power factor correction capacitors recommended with Altivar Variable Frequency drives?
Issue:
Power Factor correction capacitors on the Altivar Variable Frequency Drives.

Product Line:
Altivar Drives

Environment:
All models and serial numbers

Cause:
None

Resolution:
Schneider Electric does not recommend using power factor correction capacitors with variable frequency drives.  Capacitor banks in distribution systems with 6 pulse variable frequency drives may result in undesirable resonant currents.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: