Can a 2 pole CAFI, GFI, or EPD breaker be used to feed (2) 120 V single pole circuits with a common neutral (shared neutral)?

Article available in these languages: Spanish

Issue:
Can a 2-pole CAFI, GFI or EPD breaker be used on (2) 120 V circuits with a shared neutral?

Product Line:
Circuit Breakers

Resolution:
Yes, 2 pole CAFI, GFI, and EPD circuit breakers can be used to feed two single pole 120 Vac circuits with a common neutral.
This situation often occurs when a multi-wire conductor is used to feed the 2 circuits. These may be applied on the following systems:
  • 2p CAFI: ok for use on a 120/240 V system. NOT ok for use on a 208Y/120 V system.
  • 2p GFI and EPD: ok for use on a 120/240 V system as well as a 208Y/120 V system.
See attached letter for more information.

Schneider Electric USA

Attachment(s)
CAFI 2P Launch Details.pdf [12.89 KB]
Can a 2 pole CAFI, GFI, or EPD breaker be used to feed (2) 120 V single pole circuits with a common neutral (shared neutral)?

Article available in these languages: Spanish

Issue:
Can a 2-pole CAFI, GFI or EPD breaker be used on (2) 120 V circuits with a shared neutral?

Product Line:
Circuit Breakers

Resolution:
Yes, 2 pole CAFI, GFI, and EPD circuit breakers can be used to feed two single pole 120 Vac circuits with a common neutral.
This situation often occurs when a multi-wire conductor is used to feed the 2 circuits. These may be applied on the following systems:
  • 2p CAFI: ok for use on a 120/240 V system. NOT ok for use on a 208Y/120 V system.
  • 2p GFI and EPD: ok for use on a 120/240 V system as well as a 208Y/120 V system.
See attached letter for more information.

Schneider Electric USA

Attachment(s)
CAFI 2P Launch Details.pdf [12.89 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.