- The first step is to generate files to be transferred on the controller.
Controller program generation gives 3 files : Application.app, Application.crc and Application.map.
A folder called "visu" is created : it contains WebVisu components.
- FTP client has to be configured to transfer these files in "Binary" mode : see FileZilla screenshot in attachment.
- Now simply transfer Application.xxx files to /usr/App and all of the files in visu folder to /usr/visu.
Released for:Schneider Electric USA