{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the short circuit current rating (SCCR) of non-fused general duty safety switches when used downstream from circuit breakers?

Article available in these languages: Spanish

Issue:
SCCR of non-fusible or unfused general duty safety switches

Product Line:
Safety Switches

Environment:
General Duty Safety Switches

Cause:
Short Circuit Current Ratings

Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating because it does not contain any overcurrent protection. HOWEVER, any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available.  For higher ratings, please see information below.  Evaluation of non-fused switches used in conjunction with molded case circuit breakers has NOT been performed.

For further information, please refer to the wiring diagram label inside the switch, 2D CAD drawing, printed Digest 178(2019) page 3-5 Table 3.5, or online Digest here.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: