Issue:
SCCR of non-fusible or unfused general duty safety switches
Product Line:
Safety Switches
Environment:
General Duty Safety Switches
Cause:
Short Circuit Current Ratings
Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating because it does not contain any overcurrent protection. HOWEVER, any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available. For higher ratings, please see information below. Evaluation of non-fused switches used in conjunction with molded case circuit breakers has NOT been performed.
For further information, please refer to the wiring diagram label inside the switch, 2D CAD drawing, printed Digest 178(2019) page 3-5 Table 3.5, or online Digest here.
SCCR of non-fusible or unfused general duty safety switches
Product Line:
Safety Switches
Environment:
General Duty Safety Switches
Cause:
Short Circuit Current Ratings
Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating because it does not contain any overcurrent protection. HOWEVER, any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available. For higher ratings, please see information below. Evaluation of non-fused switches used in conjunction with molded case circuit breakers has NOT been performed.
For further information, please refer to the wiring diagram label inside the switch, 2D CAD drawing, printed Digest 178(2019) page 3-5 Table 3.5, or online Digest here.
Released for:Schneider Electric USA
Issue:
SCCR of non-fusible or unfused general duty safety switches
Product Line:
Safety Switches
Environment:
General Duty Safety Switches
Cause:
Short Circuit Current Ratings
Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating because it does not contain any overcurrent protection. HOWEVER, any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available. For higher ratings, please see information below. Evaluation of non-fused switches used in conjunction with molded case circuit breakers has NOT been performed.
For further information, please refer to the wiring diagram label inside the switch, 2D CAD drawing, printed Digest 178(2019) page 3-5 Table 3.5, or online Digest here.
SCCR of non-fusible or unfused general duty safety switches
Product Line:
Safety Switches
Environment:
General Duty Safety Switches
Cause:
Short Circuit Current Ratings
Resolution:
First, a Non-Fused Safety Switch by itself does NOT provide any short circuit current rating because it does not contain any overcurrent protection. HOWEVER, any brand of circuit breaker or fuse not exceeding the ampere rating of the switch may be used ahead of a non-fusible safety switch when there is up to 10,000A MAXIMUM of short circuit current available. For higher ratings, please see information below. Evaluation of non-fused switches used in conjunction with molded case circuit breakers has NOT been performed.
For further information, please refer to the wiring diagram label inside the switch, 2D CAD drawing, printed Digest 178(2019) page 3-5 Table 3.5, or online Digest here.
Released for:Schneider Electric USA



