Search FAQs
How are the trip unit settings determined for a Micrologic trip unit on MasterPact, PowerPacT, and legacy circuit breakers?
Issue:
Trip unit settings for a Micrologic trip unit on Masterpact, Powerpact, and legacy circuit breakers
Product Line:
Powerpact P frame, Powerpact R frame, and Masterpact circuit breakers
Resolution:
MasterPact and PowerPacT circuit breakers with Micrologic trip units are shipped with the long time pickup set at 1.0 and all other trip unit adjustments set fully counterclockwise at their lowest settings.
Actual settings required for a specific application must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system.
Trip unit settings for a Micrologic trip unit on Masterpact, Powerpact, and legacy circuit breakers
Product Line:
Powerpact P frame, Powerpact R frame, and Masterpact circuit breakers
Resolution:
MasterPact and PowerPacT circuit breakers with Micrologic trip units are shipped with the long time pickup set at 1.0 and all other trip unit adjustments set fully counterclockwise at their lowest settings.
Actual settings required for a specific application must be determined by a qualified consultant or plant engineer. A coordination study is recommended to provide coordination between all circuit breakers in the distribution system.
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: