Class 1, Division 2 use for 9001K and 9001SK operators
Issue:
Under what conditions can 9001K or 9001SK operators be used in Class 1 Division 2 applications?

Product Line:
9001K and 9001SK operators

Environment:
US Product

Cause:
Class 1 Division 2 applications do not necessitate the need for NEMA 7 or NEMA 9 control stations

Resolution:
9001K and 9001SK operators can be used for Class 1 Divsion 2 Groups A, B, C, D applications so long as all of the following restrictions are observed:
1)  Only logic (9001KA40) or power (9001KA50) reed contact blocks are used
2)  All type K or SK illuminated operators are UL approved for use in Class 1 Division 2 areas - push to test single lamp pilot lights require Y243 form code.
3)  Type KX illuminated operators do not use four lamp modules or 2 lamp modules other than the transformer type.
4)  The operators are mounted in any NEMA 4 or NEMA 13 enclosure
5)  Potentiometers are not used
 

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.