{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Why M218 can not keep the retain data after power off?
If you define a variable like "aaa", and you move it to %MW0. %MW0 is in retain area, but variable "aaa" is not a retain data, so "aaa" will over-write the %MW0 value, which cause %MW0 can not retain data. If you want variable "aaa" to keep data, you just define the variable as retain variable.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: