What's the different between Modbus TCP server and Modbus TCP slave device for M258 Ethernet?
Modbus TCP serverModbus TCP slave device
Only configure IP addressNeed to configure parameters and I/O mapping
For Modbus TCP client, all %MW address of server can be R/W.For I/O scanner, only %IW area (2~40 words) can be R/W, %QW area (2~40 words) are read only, and actual %MW address of slave device cannot be visited.
No need to configure “Unit ID”Unit ID (1~247) should be same the unit ID setting in Modbus TCP I/O scanner.
No visualized list for communicated address.Have a clear and visualized interface to monitor all communicated variables.
The connection to one client may be closed when more than 8 connections are needed.The connection to the Master client is never forcefully closed, when IPMaster Address is configured.

Please see attached ModbusTCP Slave Device explanation document.

Schneider Electric USA

Attachment(s)
Modbus TCP Slave Device.pdf [89.91 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.