Product Line:
Circuit Breakers
Environment:
Electrical Distribution Equipment
Resolution:
The Powerpact H, J, and L frame breakers are rated for 690 V if using the R interrupt letter.
This gives them 20 kAIC @ 690 V. Above 600 A, you would need to use the Compact breakers to get 690 V rated.
Circuit Breakers
Environment:
Electrical Distribution Equipment
Resolution:
The Powerpact H, J, and L frame breakers are rated for 690 V if using the R interrupt letter.
This gives them 20 kAIC @ 690 V. Above 600 A, you would need to use the Compact breakers to get 690 V rated.