Issue:
Replacement for the old PQ3620 plug-in units
Product Line:
I-Line II Busway
Environment:
Fusible Plug in Units, 200 amp, 120/208 Vac (240 Vac Max) 4-Pole, 3 Fuse + G
Cause:
There is a need to know if the PQ3620G can be used in place of the PQ3620.
Resolution:
Yes, however, the ground stab may need to be removed if used on some of the older I-line busway products that had no opening allowing for newer integral ground connection
Replacement for the old PQ3620 plug-in units
Product Line:
I-Line II Busway
Environment:
Fusible Plug in Units, 200 amp, 120/208 Vac (240 Vac Max) 4-Pole, 3 Fuse + G
Cause:
There is a need to know if the PQ3620G can be used in place of the PQ3620.
Resolution:
Yes, however, the ground stab may need to be removed if used on some of the older I-line busway products that had no opening allowing for newer integral ground connection
Released for:Schneider Electric USA
Issue:
Replacement for the old PQ3620 plug-in units
Product Line:
I-Line II Busway
Environment:
Fusible Plug in Units, 200 amp, 120/208 Vac (240 Vac Max) 4-Pole, 3 Fuse + G
Cause:
There is a need to know if the PQ3620G can be used in place of the PQ3620.
Resolution:
Yes, however, the ground stab may need to be removed if used on some of the older I-line busway products that had no opening allowing for newer integral ground connection
Replacement for the old PQ3620 plug-in units
Product Line:
I-Line II Busway
Environment:
Fusible Plug in Units, 200 amp, 120/208 Vac (240 Vac Max) 4-Pole, 3 Fuse + G
Cause:
There is a need to know if the PQ3620G can be used in place of the PQ3620.
Resolution:
Yes, however, the ground stab may need to be removed if used on some of the older I-line busway products that had no opening allowing for newer integral ground connection
Released for:Schneider Electric USA