Does Schneider offer a 1200 A QMB switch? If so, where is it used?
Issue:
Part number for a 1200A QMB switch
Product Line:
Switch
Environment:
QMB
Resolution:
The part number is QMB368W but is restricted to mounting in QED2 Switchboards with 42" and 48" wide QMB distribution sections. 42" wide QMB distribution sections are limited to qty 1, QMB368W and 48" wide are limited to qty 2, QMB368W switches. The QMB368W can not be installed in the QMB panelboards. QMB panelboards are limited to 800a main and branch QMB switches.
Part number for a 1200A QMB switch
Product Line:
Switch
Environment:
QMB
Resolution:
The part number is QMB368W but is restricted to mounting in QED2 Switchboards with 42" and 48" wide QMB distribution sections. 42" wide QMB distribution sections are limited to qty 1, QMB368W and 48" wide are limited to qty 2, QMB368W switches. The QMB368W can not be installed in the QMB panelboards. QMB panelboards are limited to 800a main and branch QMB switches.
Released for:Schneider Electric USA