Why is the web page not accessible on ATV61/71 drives?
Issue:
Accessing webpage on ATV61 ATV71 VFDs.

Product Line:
Altivar 61 and 71 drives

Environment:
All models and serial numbers with Ethernet IP option card VW3A3316

Cause:
Java 1.8 is not supported or web server services are not activated.

Resolution:
First, verify that web server services are  activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Next, check your computer's Java version, and if 1.8 or later is installed, roll back the Java version to 1.7.67.  See the document attached.

Schneider Electric USA

Attachment(s)
WEB PAGE JAVA ISSUE.docx [762.57 KB]
Why is the web page not accessible on ATV61/71 drives?
Issue:
Accessing webpage on ATV61 ATV71 VFDs.

Product Line:
Altivar 61 and 71 drives

Environment:
All models and serial numbers with Ethernet IP option card VW3A3316

Cause:
Java 1.8 is not supported or web server services are not activated.

Resolution:
First, verify that web server services are  activated via the "SERVICES" parameter:
From the main menu, navigate to the DRIVE menu -> [COMMUNICATION] -> [ETHIP] -> [SERVICES] and verify that Web server services are not deactivated.
Next, check your computer's Java version, and if 1.8 or later is installed, roll back the Java version to 1.7.67.  See the document attached.

Schneider Electric USA

Attachment(s)
WEB PAGE JAVA ISSUE.docx [762.57 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.