Issue:
What is the charging time, duty cycle, and VA requirement for the Masterpact NW and NT spring charging motors?
Product Line:
Circuit Breakers
Resolution:
Charging time: 4 seconds maximum.
Operating rate: 3 cycles per minute, maximum.
Minimum voltage: 0.85 to 1.1 times rated voltage.
Maximum power consumption: 180VA.
Released for:Schneider Electric USA