{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Will a MH36800 fit in a HCP panel?
Issue:
Breaker for I-Line panel

Product Line:
Panelboards

Environment:
I-Line HCP

Cause:
Mounting

Resolution:
Neither the MA or MH breakers will fit in the wide side of this I-Line panel. The cam foot has no where to engage the back panel. Use the HCRU or older HCW interior instead.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: