Is the use of Noalox antioxidant, for termination to Panelboards, prohibited?
Issue:
Can a Noalox antioxidant, for termination to Panelboards, prohibited?
Product Line:
NQ/ NF/ I Line/ QMB
Environment:
Installation
Cause:
Restrictions
Resolution:
The use of an antioxidant , such as Noalox, on Panelboard Main Lugs is not required.
The lugs are UL listed for use with copper or aluminum conductors without the use of ANY anti-oxidation supplement. The use of an antioxidant is not prohibited, but assurances must be made that the brand used, is a NON PETROLEUM based product. If a petroleum based product is used and comes in contact with the insulating base, the insulating base material can be degraded.
Can a Noalox antioxidant, for termination to Panelboards, prohibited?
Product Line:
NQ/ NF/ I Line/ QMB
Environment:
Installation
Cause:
Restrictions
Resolution:
The use of an antioxidant , such as Noalox, on Panelboard Main Lugs is not required.
The lugs are UL listed for use with copper or aluminum conductors without the use of ANY anti-oxidation supplement. The use of an antioxidant is not prohibited, but assurances must be made that the brand used, is a NON PETROLEUM based product. If a petroleum based product is used and comes in contact with the insulating base, the insulating base material can be degraded.
Released for:Schneider Electric USA