What are the pros and cons of using harmonic mitigating transformers compared to K-factor transformers to handle non-linear loads?
Issue:
Differences between Harmonic mitigating transformers and K-Factor transformers

Product Line:
Low Voltage Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Resolution:
A K- factor transformer is an oversized transformer with more copper to protect itself against heating from the harmonics.  A harmonic mitigating transformer is designed more like a zig-zag transformer, which can counter the harmonics within the windings. This is more effective in reducing the harmonic distortion. The K-factor will not reduce the Total Harmonic Distortion (THD).

Schneider Electric USA

Attachment(s)
7400DB0301.pdf [154.06 KB]
What are the pros and cons of using harmonic mitigating transformers compared to K-factor transformers to handle non-linear loads?
Issue:
Differences between Harmonic mitigating transformers and K-Factor transformers

Product Line:
Low Voltage Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Resolution:
A K- factor transformer is an oversized transformer with more copper to protect itself against heating from the harmonics.  A harmonic mitigating transformer is designed more like a zig-zag transformer, which can counter the harmonics within the windings. This is more effective in reducing the harmonic distortion. The K-factor will not reduce the Total Harmonic Distortion (THD).

Schneider Electric USA

Attachment(s)
7400DB0301.pdf [154.06 KB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.