Issue:
Identify how to wire a 9013 pressure switch
Product Line:
Square D™ 9013 Power Pressure Switches
Environment:
Products sold in the US
Resolution:
When looking directly at the switch you should see four terminals going from left to right. You want your power going to the outside terminals of the device. The two inside terminals should be wired to your pump/motor.
When done it should be both black wires on one side, and both red/white on the other.
Identify how to wire a 9013 pressure switch
Product Line:
Square D™ 9013 Power Pressure Switches
Environment:
Products sold in the US
Resolution:
When looking directly at the switch you should see four terminals going from left to right. You want your power going to the outside terminals of the device. The two inside terminals should be wired to your pump/motor.
When done it should be both black wires on one side, and both red/white on the other.
Released for:Schneider Electric USA
Issue:
Identify how to wire a 9013 pressure switch
Product Line:
Square D™ 9013 Power Pressure Switches
Environment:
Products sold in the US
Resolution:
When looking directly at the switch you should see four terminals going from left to right. You want your power going to the outside terminals of the device. The two inside terminals should be wired to your pump/motor.
When done it should be both black wires on one side, and both red/white on the other.
Identify how to wire a 9013 pressure switch
Product Line:
Square D™ 9013 Power Pressure Switches
Environment:
Products sold in the US
Resolution:
When looking directly at the switch you should see four terminals going from left to right. You want your power going to the outside terminals of the device. The two inside terminals should be wired to your pump/motor.
When done it should be both black wires on one side, and both red/white on the other.
Released for:Schneider Electric USA