How to obtain the nameplate information of a MiCOM relay from its settings file
Issue
User would like to verify/check the serial number, model number, hardware revision and software revision from the MiCOM settings file.

Product Line
MiCOM Relays (All)

Resolution
To view Nameplate info of a Px4x relay:
1- Open the settings file of the relay on Easergy Studio Software by double clicking on it.
2- expand system data as shown below
3- The Model number, serial number and software revision information should be visible.

Image 1

To view Nameplate info of a Px3x Relay:
1- Open the settings file of the relay on Easergy Studio Software by double clicking on it.
2- Expand Device ID and navigate to DVICE as shown below.
3- The DVICE menu will have the following parameters: Device Type, Software version, Serial number and order number.
Image 2