What extra width is needed for a Back to Back installation for a Model 6 MCC transition section?
Issue:
Extra width needed for a Back to Back installation for a Model 6 MCC transition section
Product Line:
Model 6 Motor Control Center
Environment:
Layout
Cause:
Space allocation
Resolution:
The additional width needed for bussing transition section is 12", and back to back clearance needs to be 1" apart.
Extra width needed for a Back to Back installation for a Model 6 MCC transition section
Product Line:
Model 6 Motor Control Center
Environment:
Layout
Cause:
Space allocation
Resolution:
The additional width needed for bussing transition section is 12", and back to back clearance needs to be 1" apart.
Released for:Schneider Electric USA