{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.

How can we help you today?

How is a dynamic braking resistor added to an ATV32 drive?

Article available in these languages: Spanish

Issue:
Addition of dynamic braking resistor on ATV32.

Product Line:
Altivar 32

Environment:
All

Cause:
N/A

Resolution:
Wiring:
The resistor should be wired to the PA and PB terminals on the drive.

Programming:
DRI- > CONF > FULL > FUN- > STT
Go into CONF menu, then FULL menu, then FUN menu.
Under FUN, go into STT- menu.
Set brA to [No].

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: