Search FAQs
How to calculate the IDMT Curves for MiCOM and SEPAM relays
Issue
Need to know how to calculate the IDMT curves for the MiCOM and SEPAM relays
Product Lines
MiCOM & SEPAM
Environment
Tripping IDMT Curves
Resolution
Attached are the two tools to calculate the IDMT Curves for the all the MiCOM and all the SEPAM relays.
Note: The tools are not interchangeable. Unprotect sheets to work with formulas. Charts are not included.
Conversion of TMS (Time Multiplier Setting) to Time delay (seconds):
![TMS graph TMS graph](https://ckm-content.se.com/ckmContent/servlet/servlet.ImageServer?id=0151H000008zqP4QAI&oid=00DA0000000abSm)
Need to know how to calculate the IDMT curves for the MiCOM and SEPAM relays
Product Lines
MiCOM & SEPAM
Environment
Tripping IDMT Curves
Resolution
Attached are the two tools to calculate the IDMT Curves for the all the MiCOM and all the SEPAM relays.
Note: The tools are not interchangeable. Unprotect sheets to work with formulas. Charts are not included.
Conversion of TMS (Time Multiplier Setting) to Time delay (seconds):
Released for:Schneider Electric USA
Attachment(s)