Video: How do you change the coil on a NEMA type S starter and change from common control to separate control?
Issue:
Is there an instruction guide to changing the coil on a NEMA starter?
Product Line:
NEMA Type S starters
Environment:
Products sold in the US
Resolution:
Note: Tighten all screws to recommended torque settings found on the corresponding instruction bulletins. (size 1 bulletin attached for reference).
Is there an instruction guide to changing the coil on a NEMA starter?
Product Line:
NEMA Type S starters
Environment:
Products sold in the US
Resolution:
- Remove all live power to the controller.
- Remove the wires from the coil terminals.
- Remove start cover plate screws and cover plate.
- Pull coil straight up (this will also remove the armature and magenet assemblies from the power plant. These will be re-installed in the same manner).
- Re-install armature and magnet assembly from step 4 above.
- Insert completed assembly back into power plant and re-install cover plate and previously removed wiring per your wiring diagram.
Note: Tighten all screws to recommended torque settings found on the corresponding instruction bulletins. (size 1 bulletin attached for reference).