Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Per the NEC, what are the standard ampere ratings of fixed-trip circuit breakers (600Vac maximum)?
Issue:
Where do circuit breaker amp ratings come from?

Product Line:
Circuit Breakers

Resolution:
Per NEC 240.6, the standard ampere rating for inverse time, fixed-trip circuit breakers, 600Vac maximum, shall be considered as follows:
15202530354045
5060708090100110
125150175200225250300
350400450500600700800
1000120016002000250030004000
50006000

The use of inverse time circuit breakers with nonstandard ampere ratings shall be permitted.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings