Why can't I upload my IEC program from my Concept PLC?
Issue:
IEC code in the PLC not available for upload.

IEC
Product Line:
Concept programming software.

Cause:
Either the project was downloaded before Concept 2.5 SR2 which is when IEC upload was added or
The IEC upload switch was not engaged when the project was originally downloaded.

Resolution:
There is no workaround for this problem.
The customer can avoid it in the future by opening the project offline and going to <Project><Code generation options...> and
checking <Include IEC upload information>.  This should be followed by a full download to the PLC.

Schneider Electric USA

Why can't I upload my IEC program from my Concept PLC?
Issue:
    IEC code in the PLC not available for upload.

IEC
Product Line:
    Concept programming software.

Cause:
     Either the project was downloaded before Concept 2.5 SR2 which is when IEC upload was added or
     The IEC upload switch was not engaged when the project was originally downloaded.

Resolution:
     There is no workaround for this problem.
     The customer can avoid it in the future by opening the project offline and going to <Project><Code generation options...> and 
        checking <Include IEC upload information>.  This should be followed by a full download to the PLC.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.