What are the recommended wire sizes for the Altivar 600 Process Drive?

Article available in these languages: Japanese

You would normally size the wire according to NEC and use a rating of 125% of the input line current for the rated drive.  See below for the wire size recommendation based on Frame size.

img1
f4-6
https://www.se.com/us/en/download/document/EAV64301/