Issue:
Lug kit for a 400A NQ main lug panel that has 2 separate barrels that will accept a 3/0 wire to 750mcm
Product Line:
Panelboards
Environment:
NQ panelboards
Cause:
Additional wire termination
Resolution:
The standard NQ, 400A NQ panel comes with a "snowman" lug which has adjoining circles good for either (1) 1/0-750 or (2) 1/0-350. If separate barrels are needed, order the panel with sub feed lugs. It will have (2) separate barrels with each good for 1/0-750.
Lug kit for a 400A NQ main lug panel that has 2 separate barrels that will accept a 3/0 wire to 750mcm
Product Line:
Panelboards
Environment:
NQ panelboards
Cause:
Additional wire termination
Resolution:
The standard NQ, 400A NQ panel comes with a "snowman" lug which has adjoining circles good for either (1) 1/0-750 or (2) 1/0-350. If separate barrels are needed, order the panel with sub feed lugs. It will have (2) separate barrels with each good for 1/0-750.
Released for:Schneider Electric USA
Issue:
Lug kit for a 400A NQ main lug panel that has 2 separate barrels that will accept a 3/0 wire to 750mcm
Product Line:
Panelboards
Environment:
NQ panelboards
Cause:
Additional wire termination
Resolution:
The standard NQ, 400A NQ panel comes with a "snowman" lug which has adjoining circles good for either (1) 1/0-750 or (2) 1/0-350. If separate barrels are needed, order the panel with sub feed lugs. It will have (2) separate barrels with each good for 1/0-750.
Lug kit for a 400A NQ main lug panel that has 2 separate barrels that will accept a 3/0 wire to 750mcm
Product Line:
Panelboards
Environment:
NQ panelboards
Cause:
Additional wire termination
Resolution:
The standard NQ, 400A NQ panel comes with a "snowman" lug which has adjoining circles good for either (1) 1/0-750 or (2) 1/0-350. If separate barrels are needed, order the panel with sub feed lugs. It will have (2) separate barrels with each good for 1/0-750.
Released for:Schneider Electric USA