Issue:
SCF3 fault threshold at which the drive trips
Product Line:
ATV630, ATV650, ATV930, Altivar process
Environment:
All
Cause:
N/A
Resolution:
When the determined differential current of the three output phases is greater than
25% of the nominal inverter current, the inverter is switched off with fault message
"SCF3".
SCF3 fault threshold at which the drive trips
Product Line:
ATV630, ATV650, ATV930, Altivar process
Environment:
All
Cause:
N/A
Resolution:
When the determined differential current of the three output phases is greater than
25% of the nominal inverter current, the inverter is switched off with fault message
"SCF3".
Released for:Schneider Electric USA



