Issue:
How many HQO Load centers can I install in an I Line panelboard? Is there a limit ?
Product Line:
I Line panelboard and accessories
Environment:
Application
Cause:
Clarification
Resolution:
There is a maximum of HQO distribution load centers allowed which = 7 . Since there are a max of 6, 1 pole spaces per load center, the maximum amount of QO Branch breakers that could be added would = 42 . This is due to the solid neutral not being able to support more than that.
How many HQO Load centers can I install in an I Line panelboard? Is there a limit ?
Product Line:
I Line panelboard and accessories
Environment:
Application
Cause:
Clarification
Resolution:
There is a maximum of HQO distribution load centers allowed which = 7 . Since there are a max of 6, 1 pole spaces per load center, the maximum amount of QO Branch breakers that could be added would = 42 . This is due to the solid neutral not being able to support more than that.