How do I perform ATV630 and ATV930 Basic Programming?

Article available in these languages: Spanish, Korean

Issue:
Basic Programming on an Altivar Process Drive.

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive 

Cause:
Initial setup / maintenance

Resolution:
Using the keypad or our SoMove programming software, be sure to go through the Simply Start Menu to perform your basic settings:

From the Main Menu select [Simply start]:

[Motor Standard] bFr -            50Hz IEC or 60Hz NEMA- motor nameplate

[Nominal motor power] nPr -   Motor HP - motor nameplate

[Nom Motor Voltage] UnS -      Motor voltage - motor nameplate

[Nom Motor Current] nCr -       Motor FLA - motor nameplate

[Nominal Motor Freq] FrS -      60Hz in the US - motor nameplate

[Nominal Motor Speed] nSP -   Actual motor max speed, not Synchronous speed unless it is a synchronous motor - motor nameplate

[2/3-Wire Control] tCC -           Factory default is '2-Wire Control' 

[Max Frequency] tFr -              Max frequency of the motor, usually 60Hz - motor nameplate

[Autotuning] tUn -                    No Action, Apply Autotuning, Erase Autotuning 

[Autotuning Status] tUS -         Displays 'Not Done' unless Autotuning is performed

[Motor Th Current] ItH -            Motor thermal current - motor nameplate - used to set the motor overload protection level

[Acceleration] ACC -                 Acceleration time in seconds

[Deceleration] dEC -                 Deceleration time in seconds

[Low Speed] LSP -                    Minimum speed, drive will never run lower than this speed when given a run command

[High Speed] HSP -                  Maximum speed, drive will never run higher than this speed when given a run command


In many instances these parameters will be enough to sufficiently program a drive. If any further programming is required (such as PID, command/reference switching, hoisting, etc), please refer to the applicable Programming Manual for your drive.

Refer to the applicable manual for further details:
ATV600 series Programming Manual 
ATV900 series Programming Manual 

 

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

 

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

 

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.