{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Can MDGF be combined with ZSI?
Issue:
ZSI on MDGF systems

Product Line:
Circuit breakers

Resolution:
On MDGF systems:
  • In a Main-Tie-Main system, the main breaker cannot be short time ZSI restrained by the tie breaker.
  • Since the main circuit breaker cannot be restrained on short time, it must be ZSI self restrained on the short time function.
  • The main circuit breaker can be ground fault restrained by the feeder breakers.
  • Installation of GF ZSI has no effect on MDGF and MDGF has no effect on GF ZSI.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: