{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Video: How do I program an ATV320 to use the dial of drive as speed and Digital Input 1 (DI1) terminal as start and stop control?

Article available in these languages: Finnish

Issue:
ATV320 to use the dial of drive as speed reference and Digital Input 1 (DI1) terminal as start/stop control

Product Line:
Altivar 320, ATV320

Environment:
All

Cause:
Programming setup

Resolution:



From Main Menu, press enter.
Scroll down to CONF and press enter.
Scroll down to FULL and press enter.
Scroll down to CTL and press enter.
Under CTL, set CHCF to SEP.
Set FR1 to A1U1.
Set CD1 to TER.

From the normal status display, press enter twice to then adjust the speed reference value as a % of the LSP-HSP range.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.