Issue:
Can you field install a 200% neutral or add additional neutral bars to I-line panels?
Product Line:
HCM, HCP, HCPSU, HCRU, HCW, HCN I-line panelboards
Environment:
Products sold in North America
Resolution:
No, you cannot field install or modify the neutral capacity. This would void the UL label.
The panel would need to be ordered factory installed with a 200% Neutral. Adding the 200% rated neutral will double the terminal capacity in most cases.