{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Can I synchronize the M580 PLC clock by BMENOC03X1 NTP service ?

Issue:
Can I synchronize the M580 PLC clock by BMENOC0301/11 NTP service ?

Product Line:
M580

Environment:
EcoStruxure Control Expert

Resolution:
In order for the time on the CPU module to synchronize with the BMENOC NTP service, you need to enable the network time service, in the DTM browser of the BMENOC, ,then select the checkbox  "Update CPU time with this module".
The project will need to be built and downloaded to the CPU.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: