Which explicit command is used to read the IP address of BMENOP0300 in Unity Pro
The IP address can be read by using explicit command Read_Var.
In the ADDM the address would be 'r.m.c.server address'
Here r is rack number, m is module slot of BMENOP0300 module, c is channel & server address is "100".
So the syntax would '0.3.0.100' where 3 is module slot and 100 is server address in the BMENOP0300 module.

Now to read the IP address the modus data mapping is at Offset + 5 for ( IP1 & IP2 ), Offset +6 for ( IP3 & IP4 ).
Note that here the offset starts from zero, Also we need to use Unity Pro V12 so as to work on BMENOP0300 module.