How does the RTC stay on and counting on the M580 when there is a power outage?
Issue:
How long will the RTC be running for when there is a power outage?

Product Line:
M580

Resolution:
Clock Back-Up
The accuracy of the real-time clock is maintained for 4 weeks when the CPU power is turned off if
the temperature is below 45 °C (113 °F). If the temperature is higher, the back-up time is shorter.
The real-time clock back-up does not need any maintenance.
If the back-up power is too low, system bit %S51 is set to 1. This value indicates a loss of time when
the power supply was OFF.

Schneider Electric USA

How does the RTC stay on and counting on the M580 when there is a power outage?
Issue:
How long will the RTC be running for when there is a power outage?

Product Line:
M580

Resolution:
Clock Back-Up
The accuracy of the real-time clock is maintained for 4 weeks when the CPU power is turned off if
the temperature is below 45 °C (113 °F). If the temperature is higher, the back-up time is shorter.
The real-time clock back-up does not need any maintenance.
If the back-up power is too low, system bit %S51 is set to 1. This value indicates a loss of time when
the power supply was OFF.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.