{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Can a vertically mounted main breaker in an I-line panelboard be replaced?

Article available in these languages: Spanish

Issue:
Replacement of I-Line main circuit breaker

Product line:
I-Line panelboards

Environment:
Maintenance

Resolution:
You may ONLY replace a vertically mounted main breaker in an I-line panelboard with the same model breaker.  For example, the MAP36600 is obsolete and could NOT be replaced by a current series M-frame like the MGP36600.  Consider replacing the panelboard.

Keywords:
I-line panelboards vertical vertically mounted main breaker replacement Powerpact legacy HCN HCM HCW HCWM HCWM-U HCP-SU HCP HCR-U

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: