Search FAQs
Can a vertically mounted main breaker in an I-line panelboard be replaced?
Issue:
Replacement of I-Line main circuit breaker
Product line:
I-Line panelboards
Environment:
Maintenance
Resolution:
You may ONLY replace a vertically mounted main breaker in an I-line panelboard with the same model breaker. For example, the MAP36600 is obsolete and could NOT be replaced by a current series M-frame like the MGP36600. Consider replacing the panelboard.
Keywords:
I-line panelboards vertical vertically mounted main breaker replacement Powerpact legacy HCN HCM HCW HCWM HCWM-U HCP-SU HCP HCR-U
Replacement of I-Line main circuit breaker
Product line:
I-Line panelboards
Environment:
Maintenance
Resolution:
You may ONLY replace a vertically mounted main breaker in an I-line panelboard with the same model breaker. For example, the MAP36600 is obsolete and could NOT be replaced by a current series M-frame like the MGP36600. Consider replacing the panelboard.
Keywords:
I-line panelboards vertical vertically mounted main breaker replacement Powerpact legacy HCN HCM HCW HCWM HCWM-U HCP-SU HCP HCR-U
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: