Issue:
How the events are managed and stored in the event buffer of BMXNOR0200 Modicon X80 module
Product Line:
BMXNOR0200H
Environment:
All
Resolution:
There are two modes of events storage
1. Store All Events
Here all the events are stored until they reach the limit of storage which can be set by the user.
If still, the events are coming they get lost.
There is one option called " Delete the oldest events " if selected then the FIFO strategy is implemented in the event buffer. if this is not selected then the additional events are lost.
2. Store only recent events
Here only the recent event for the data point is stored, so if there are 5 events for a single data point
then the fifth event which is the recent one will get stored and all others are deleted
How the events are managed and stored in the event buffer of BMXNOR0200 Modicon X80 module
Product Line:
BMXNOR0200H
Environment:
All
Resolution:
There are two modes of events storage
1. Store All Events
Here all the events are stored until they reach the limit of storage which can be set by the user.
If still, the events are coming they get lost.
There is one option called " Delete the oldest events " if selected then the FIFO strategy is implemented in the event buffer. if this is not selected then the additional events are lost.
2. Store only recent events
Here only the recent event for the data point is stored, so if there are 5 events for a single data point
then the fifth event which is the recent one will get stored and all others are deleted
Released for:Schneider Electric USA
Issue:
How the events are managed and stored in the event buffer of BMXNOR0200 Modicon X80 module
Product Line:
BMXNOR0200H
Environment:
All
Resolution:
There are two modes of events storage
1. Store All Events
Here all the events are stored until they reach the limit of storage which can be set by the user.
If still, the events are coming they get lost.
There is one option called " Delete the oldest events " if selected then the FIFO strategy is implemented in the event buffer. if this is not selected then the additional events are lost.
2. Store only recent events
Here only the recent event for the data point is stored, so if there are 5 events for a single data point
then the fifth event which is the recent one will get stored and all others are deleted
How the events are managed and stored in the event buffer of BMXNOR0200 Modicon X80 module
Product Line:
BMXNOR0200H
Environment:
All
Resolution:
There are two modes of events storage
1. Store All Events
Here all the events are stored until they reach the limit of storage which can be set by the user.
If still, the events are coming they get lost.
There is one option called " Delete the oldest events " if selected then the FIFO strategy is implemented in the event buffer. if this is not selected then the additional events are lost.
2. Store only recent events
Here only the recent event for the data point is stored, so if there are 5 events for a single data point
then the fifth event which is the recent one will get stored and all others are deleted
Released for:Schneider Electric USA















