Is the Model 6 motor control center (MCC) available for a 240V delta system with a high leg?
Issue:
Can you get a MCC rated for a 120/240 3 phase 4 wire high leg system?

Product Line:
Motor Control Center - MCC

Environment:
Model 6

Cause:
Application requirement delta high leg

Resolution:
In Product selectors, the MCC would be entered as 240 v 3Ph 3W. This way the CPT's in the units will be correct. You must put a note in the "Gen Req" tag window- "This is a 240 volt 4 wire with a B-High leg". The plant will then mark this and add a red sign on the MCC about the High Leg. You will need to identify which phase is the high leg. Please be reminded this may impact the delivery code.

Schneider Electric USA

Is the Model 6 motor control center (MCC) available for a 240V delta system with a high leg?
Issue:
Can you get a MCC rated for a 120/240 3 phase 4 wire high leg system? 

Product Line:
Motor Control Center - MCC

Environment:
Model 6

Cause:
Application requirement delta high leg

Resolution:
In Product selectors, the MCC would be entered as 240 v 3Ph 3W. This way the CPT's in the units will be correct. You must put a note in the "Gen Req" tag window- "This is a 240 volt 4 wire with a B-High leg".   The plant will then mark this and add a red sign on the MCC about the High Leg. You will need to identify which phase is the high leg. Please be reminded this may impact the delivery code.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.