Issue:
Need to use Multi 9 breakers in a hazardous location where it may be exposed to flammable liquid or gases.
Product line:
DIN rail mounted circuit breaker enclosures
Environment:
Multi 9 circuit breakers, Kaedra enclosures
Cause:
There may be volatile ignitable liquid or gases in the area and the breakers need to be protected.
Resolution:
No, Schneider Electric does not offer any enclosures for Multi 9 breakers that are Class 1, Div 2. The Kaedra enclosures for Multi 9 breakers are Class 2 and thus only qualify as weatherproof. They conform to IEC 670 and are NOT UL/CSA listed.
Need to use Multi 9 breakers in a hazardous location where it may be exposed to flammable liquid or gases.
Product line:
DIN rail mounted circuit breaker enclosures
Environment:
Multi 9 circuit breakers, Kaedra enclosures
Cause:
There may be volatile ignitable liquid or gases in the area and the breakers need to be protected.
Resolution:
No, Schneider Electric does not offer any enclosures for Multi 9 breakers that are Class 1, Div 2. The Kaedra enclosures for Multi 9 breakers are Class 2 and thus only qualify as weatherproof. They conform to IEC 670 and are NOT UL/CSA listed.