Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
Video: How to install compression lug kits onto a PowerPacT B frame breaker
Issue:
How do you install the compression lugs on a B frame breaker?

Product Line:
Molded Case Circuit Breakers

Resolution:
Remove the green connection system cover (put a screwdriver or similar flat tool into slot in the connecter and push out) and the currently installed lug kit (put a screwdriver or similar flat tool into the gap between the lug kit and breaker on the back, and push the lug kit out). Then install the terminal nut kit onto the breaker (if not already installed). Slide the heat shrink sleeve over the conductor, then slide the conductor into the compression lug and crimp the lug. Then you would slide the heat shrink sleeve into place over the conductor and the lug, and then heat it to shrink it (alternatively, you can use the interphase barriers or long terminal shield instead of the heat shrink). Once you have your desired insulator installed, you would place the compression lug against the terminal nut kit and use the screw provided with the terminal nut kit to screw it into place. Finally, you would reinstall the green connection system cover. For further information, see the attached installation bulletin or see the video below:

Schneider Electric USA

Attachment(s)
B Frame Compression Lugs.pdf [925.05 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: