Can you fine tune the trip settings of Powerpact H, J and L frame breakers?

Article available in these languages: Spanish

Issue:
Can you adjust the Micrologic trip unit of electronic H, J and L frame breakers in 1 A increments?

Product line:
Molded case circuit breakers

Environment:
Powerpact H, J and L frame breakers with Micrologic trip units

Resolution:
You must have the Micrologic ammeter 5.2A/6.2A or energy 5.2E/6.2E trip unit in order to fine tune the settings.  The keypad can be used to make fine adjustments in 1 A steps below the maximum value defined by the setting on the dial.

See the attached document for instructions from our Micrologic trip unit bulletin 48940-312-01 for a step-by-step guide on making these settings.

Schneider Electric USA

Attachment(s)

Fine Tuning Micrologic Settings.pdfFine Tuning Micrologic Settings.pdf [56.88 KB]