Issue:
How do you install an auxiliary or alarm switch (S29450) into a PowerPacT H or J Frame circuit breaker?
Product Line:
Molded Case Circuit Breakers
Resolution:
Make sure the breaker is in the tripped position, and then remove the two screws on the cover and remove the cover. Place the switch in one of the two outer slots for the OF or auxiliary functionality (changes state when the breaker contacts change state) or in the right slot on the left side of the breaker for the SD or alarm functionality (changes state when the breaker trips). For more information, see the video below or the attached instruction bulletin:
How do you install an auxiliary or alarm switch (S29450) into a PowerPacT H or J Frame circuit breaker?
Product Line:
Molded Case Circuit Breakers
Resolution:
Make sure the breaker is in the tripped position, and then remove the two screws on the cover and remove the cover. Place the switch in one of the two outer slots for the OF or auxiliary functionality (changes state when the breaker contacts change state) or in the right slot on the left side of the breaker for the SD or alarm functionality (changes state when the breaker trips). For more information, see the video below or the attached instruction bulletin: