Issue
The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.

Product Line
Link150, EGX150

Environment
EGX150 serial connections

Cause
The EGX150 does not use the standard RS-485 connector.

Resolution
Pin NumberColourSignal nameDescription
1Orange/White stripedRx-Receive Data -
2OrangeRx+Receive Data +
3NCNo Connection
4BlueTx+Transmit Data +
5Blue/white stripedTx-Transmit Data -
6NCNo Connection
7NCNo connection
8GNDGround













Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
Cut the other end (that is to be connected to your slave device) to expose the wires.

2-Wire RS-485 connection:
Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)
RS485 2-Wire Connection Diagram

4-Wire RS-485 connection:
RJ45 Pin Number MasterSlave
1Rx-Tx-
2Rx+Tx+
4Tx+Rx+
5Tx-Rx-







RS485 4-Wire Connection Diagram

Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.