Issue:
How do you install the terminal nut kits for the PowerPacT H and J frame circuit breakers?
Product Line:
Molded Case Circuit Breakers
Resolution:
First, you will remove the already installed lugs (if applicable) by inserting a flathead screwdriver into the small slot on the top of the lug and leveraging it out of the breaker. You will then place the terminal nut insert in the same place. You will then bring in the conductor and bolt it to the nut with the provided screw. For more information, see the attached instruction bulletin or the instructional video below:
How do you install the terminal nut kits for the PowerPacT H and J frame circuit breakers?
Product Line:
Molded Case Circuit Breakers
Resolution:
First, you will remove the already installed lugs (if applicable) by inserting a flathead screwdriver into the small slot on the top of the lug and leveraging it out of the breaker. You will then place the terminal nut insert in the same place. You will then bring in the conductor and bolt it to the nut with the provided screw. For more information, see the attached instruction bulletin or the instructional video below:
Released for:Schneider Electric USA