{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
ATV212 is configured to communicate via Modbus. How to reset the drive when the drive is showing an error?
If you can communicate with the drive while display shows error, then you can reset the drive fault over modbus using bit 13 of command word.
See attached page from ATV212 manual.
The fault of course must be "resetable". List of all resetable faults can be found in ATV212 programming manual.

Schneider Electric USA

Attachment(s)
Extracted pages from ATV212 Modbus_manual_EN_S1A53844_01.pdf [68.14 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: