Search FAQs
How to setup a run status on an ATS22 softstart?
Issue:
ATS22 run status setup
Product Line:
Altistart 22
Environment:
All
Cause:
Run status
Resolution:
Go into I/O menu.
Find R1 relay parameter.
R1 can be used as a run status.
R1 can be programmd to the following:
NSTP - starting - Relay is not energized at stop and is energized at all other times.
Run - running - Relay is energized when the bypass contactor is closed
ATS22 run status setup
Product Line:
Altistart 22
Environment:
All
Cause:
Run status
Resolution:
Go into I/O menu.
Find R1 relay parameter.
R1 can be used as a run status.
R1 can be programmd to the following:
NSTP - starting - Relay is not energized at stop and is energized at all other times.
Run - running - Relay is energized when the bypass contactor is closed
Released for:Schneider Electric USA
Explore more
Range:
Explore more
Range: