Can a 3 phase contactor or starter be used on a single phase application?
Issue:
3 Phase contactor used in single phase explanation

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
8502 and 8536

Resolution:
For our contactors any two legs can be used to make and break the single phase load.
For starters how the device should be set up will depend on the type of overload relay.
  • For starters with melting alloy overloads any two legs can be wired, but there will need to be thermal units in all three legs.
  • For devices with solid state overload relays current has to pass through all three legs. This can be accomplished by looping a leg through two poles on the starter.
  • For devices with a TeSys T motor management controller you have to wire through the outter two legs, and program the TeSys T for a single phase load.

Schneider Electric USA

Can a 3 phase contactor or starter be used on a single phase application?
Issue:
3 Phase contactor used in single phase explanation

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
8502 and 8536

Resolution:
For our contactors any two legs can be used to make and break the single phase load.
For starters how the device should be set up will depend on the type of overload relay. 
  • For starters with melting alloy overloads any two legs can be wired, but there will need to be thermal units in all three legs. 
  • For devices with solid state overload relays current has to pass through all three legs. This can be accomplished by looping a leg through two poles on the starter. 
  • For devices with a TeSys T motor management controller you have to wire through the outter two legs, and program the TeSys T for a single phase load. 

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.