{}

Our Brands

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
How can I activate minute pulse time synchronisation in Easergy P3 and how does it work?

In menu “Clock sync”, set parameter “Minute sync pulse DI” to the digital (or virtual) input which will give the pulse. Two consecutive minute pulses must be given before the synchronisation start. The clock will be adjusted to the nearest minute each time the pulse is received, i.e. seconds and ms will be reset. Minute pulse can also be received with a GOOSE signal.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.