{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
The vertical cable manager is interfering with cage nut holes and the ability to mount equipment into the NetShelter cabinet, what's wrong?
Issue:
After installing finger-style cable managers the customer cannot install equipment.

Product Line:
AR7580A, AR7585, AR7588

Environment:
All serial numbers.

Cause:
The cable manager interferes with the mounting holes on the rails.

Resolution:
Intereference with the mounting holes on the rails is caused by one of two possible installation errors:

1) After attaching the cable manager to the rail the cable manager must slide towards the side of the cabinet, this will draw it away from the equipment mounting holes.
AR7580A - See installation step 6: https://www.apc.com/salestools/JKUR-948NBR/JKUR-948NBR_R1_EN.pdf
AR7585 - See installation step 6: https://www.apc.com/salestools/MLAN-8ZRM62/MLAN-8ZRM62_R1_EN.pdf
AR7588 - See installation step 6: https://www.apc.com/salestools/MLAN-8ZSRDH/MLAN-8ZSRDH_R1_EN.pdf

2) When installing the cable managers in the rear of a cabinet the accessory/PDU mounting rails must be moved out of the way. The cable managers cannot be installed atop the accessory/PDU mounting rails.

Schneider Electric USA

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: